What this MCCB carries
The Siemens SENTRON 3VA2040-8HL32-0AA0 is a 3-pole molded case circuit breaker rated for 40 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It uses an ETU320 electronic trip unit, which means you get adjustable overload and short-circuit protection curves, not a fixed thermal-magnetic bimetal. Breaking capacity hits 440 kA at 240 V, 330 kA at 415 V, and still 52.5 kA at 690 V, so it handles high-fault utility feeds or transformer secondaries without cascading upstream.
Panel fit and mounting
The 3VA2040-8HL32-0AA0 measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard MCCB footprint that drops into a SENTRON panel or any DIN-rail-mounting baseplate. Front IP40 keeps dust out of the trip-unit interface; the enclosure is designed for line-side protection in distribution boards. No undervoltage release or communication module on this variant, so it's a straight power path with the trip unit doing the decision-making.