Skip to main content
Siemens 3VA2116-0HL32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-0HL32-0AA0 SENTRON MCCB, 160 A, 440 kA at 41

MPN3VA2116-0HL32-0AA0
Active

Siemens SENTRON 3VA2116-0HL32-0AA0, molded case circuit breaker, 3-pole, 160 A continuous, ETU320 electronic trip unit, 440 kA breaking capacity at 415 V AC, IP40 front protection.

$494.03Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2116-0HL32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2116-0HL32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.19.7 W
3VA2116-0HL32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2116-0HL32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-0HL32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2116-0HL32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-0HL32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens 3VA2116-0HL32-0AA0 is a 3-pole SENTRON molded case circuit breaker rated for 160 A continuous current with an ETU320 electronic trip unit. That 160 A holds flat across the full ambient range from 40 °C to 70 °C — no derating curve to chase in a warm panel. The 440 kA breaking capacity at 415 V AC means it can interrupt fault currents up to that level without cascading upstream; at 690 V AC the rating drops to 187 kA, still well above typical industrial service-entrance levels.

The 3VA2116-0HL32-0AA0 measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard SENTRON 3VA2 frame footprint. Operating temperature range is -25 °C to 70 °C; storage range -40 °C to 80 °C.

Frequently asked questions

Where can I buy 3VA2116-0HL32-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position.

What are the key ratings for 3VA2116-0HL32-0AA0?

160 A continuous current, 440 kA breaking capacity at 415 V AC, 187 kA at 690 V AC, ETU320 electronic trip unit, 3-pole, IP40 front protection, 800 V insulation voltage.

Will 3VA2116-0HL32-0AA0 drop into a panel specified around 5SQ2370-2YA05?

The 3VA2116-0HL32-0AA0 is a different frame and trip platform than the 5SQ2370 series. Verify mounting footprint and busbar spacing before substitution — the 105 mm width and 86 mm depth are standard SENTRON 3VA2 dimensions, not necessarily matching the 5SQ2370 panel cutout.

MPN
3VA2116-0HL32-0AA0