Skip to main content
Siemens 3VA2116-0HN46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-0HN46-0AA0 SENTRON MCCB, 160 A, 440 kA at 41

MPN3VA2116-0HN46-0AA0
Active

Siemens SENTRON 3VA2116-0HN46-0AA0, molded case circuit breaker, 4-pole, 160 A continuous, ETU350 release, 440 kA at 415 V AC, 187 kA at 690 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2116-0HN46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2116-0HN46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.19.7 W
3VA2116-0HN46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2116-0HN46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-0HN46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2116-0HN46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-0HN46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

The 3VA2116-0HN46-0AA0 is a Siemens SENTRON molded case circuit breaker (MCCB) rated for 160 A continuous current, with a maximum breaking capacity of 440 kA at 415 V AC and 187 kA at 690 V AC. The N-conductor protection is configurable to OFF, 50%, or 100% of the phase current — useful for sizing the neutral on systems with harmonic content.

There is no official successor order code — the part is current, not replaced. If you need a functional cross-reference within the same SENTRON 3VA family, the closest peer is the 3VA1112-5EE32-0AA0, but that is a different frame size and rating; the 3VA2116-0HN46-0AA0 is the 160 A, 4-pole variant with the high-breaking ETU350 release. Do not assume a drop-in swap without checking the frame dimensions and terminal layout.

At 86 mm deep, this MCCB fits standard 200 mm deep switchboards with clearance for rear-connected busbars. The 140 mm width is a 4-pole frame — plan for a 4-module wide cutout in the mounting plate. Maximum power loss is 19.7 W, so ventilation in the enclosure should account for that heat at full load.

Frequently asked questions

Where can I buy 3VA2116-0HN46-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 3VA2116-0HN46-0AA0 at 415 V and 690 V?

The breaking capacity is 440 kA at 415 V AC and 187 kA at 690 V AC. The 440 kA figure is exceptionally high — suitable for installations with very high available fault current, such as large transformer secondaries or industrial main switchboards.

Does 3VA2116-0HN46-0AA0 have an undervoltage release or communication function?

No. This breaker has no undervoltage release and no communication function. It also lacks ground-fault monitoring. It is a basic line-protection MCCB with an electronic trip unit.

MPN