Skip to main content
Siemens 3VA2116-0HL46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-0HL46-0AA0 SENTRON MCCB, 160 A, 4-Pole, 440

MPN3VA2116-0HL46-0AA0
Active

Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2116-0HL46-0AA0, 160 A, 4-pole, ETU320 electronic trip, 440 kA at 415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2116-0HL46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2116-0HL46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.19.7 W
3VA2116-0HL46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2116-0HL46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-0HL46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2116-0HL46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-0HL46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

The Siemens 3VA2116-0HL46-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 160 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Four poles, line-protection design, with an ETU320 electronic overcurrent release that gives adjustable N-conductor protection (OFF, 50%, 100%). Breaking capacity hits 440 kA at 415 V AC and 187 kA at 690 V AC — that is the interrupting rating the breaker can clear under fault without welding contacts or cascading upstream. Dimensions are 181 mm high, 140 mm wide, 86 mm deep.

How the ETU320 release shapes selectivity

The ETU320 is an electronic trip unit — not a thermal-magnetic. That means the long-time, short-time, and instantaneous pickup bands are adjustable, which matters for selective coordination downstream. The N-conductor protection can be set to OFF, 50%, or 100% of the phase pickup, giving the panel designer control over ground-fault coordination without a separate module.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

440 kA at 415 V AC, and 187 kA at 690 V AC — these are the interrupting ratings the breaker can clear under fault.

What is the continuous current rating and does it derate with temperature?

Rated 160 A continuous from 40 °C through 70 °C ambient — no derating required across that entire range.

Where can I buy 3VA2116-0HL46-0AA0 and how is it quoted?

Sourced through independent distribution channels. Quoted to order against an RFQ; availability and current pricing are confirmed at quote time.

MPN
3VA2116-0HL46-0AA0