Skip to main content
Siemens 3VA2125-0HL32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2125-0HL32-0AA0 MCCB, 25 A, 440 kA at 415 V

MPN3VA2125-0HL32-0AA0
Active

Siemens SENTRON 3VA2125-0HL32-0AA0, molded case circuit breaker, 3-pole, 25 A continuous, ETU320 release, 440 kA at 415 V, 690 V rated voltage.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2125-0HL32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2125-0HL32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.0.5 W
3VA2125-0HL32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2125-0HL32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2125-0HL32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2125-0HL32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2125-0HL32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2125-0HL32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, with a continuous current of 25 A and an ETU320 electronic overcurrent release. The breaking capacity hits 440 kA at 415 V and 187 kA at 690 V — that means it can safely clear a fault current up to those levels without the arc flashing over or the case rupturing, which is what you need when the available short-circuit current on the bus is high.

The continuous current rating of 25 A holds across the full ambient range from 40 °C to 70 °C — no derating needed for elevated panel temperatures, which simplifies panel design in hot environments like boiler rooms or enclosed switchgear. The minimum setting is 38 A, so this breaker is sized for a feeder or branch circuit where the load current stays between 38 A and 300 A maximum.

Dimensions are 105 mm wide, 181 mm tall, and 86 mm deep — a standard 3-pole MCCB footprint that drops into a DIN-rail or panel-mount enclosure without surprises. Operating temperature range is -25 °C to 70 °C, storage from -40 °C to 80 °C. Power loss is a negligible 0.5 W maximum, so no special ventilation is needed.

Frequently asked questions

Where can I buy 3VA2125-0HL32-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2125-0HL32-0AA0?

The breaking capacity is 440 kA at 415 V and 187 kA at 690 V, which covers most high-fault industrial distribution panels.

What does the ETU320 release do?

The ETU320 is an electronic overcurrent release that provides adjustable trip settings for overload and short-circuit protection, allowing fine-tuning to the load without swapping the breaker.

MPN
3VA2125-0HL32-0AA0