Skip to main content
Siemens 3VA2125-5HM32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2125-5HM32-0AA0 SENTRON MCCB, 25 A, 3-Pole, 187 k

MPN3VA2125-5HM32-0AA0
Active

Siemens SENTRON molded case circuit breaker, 3VA2125-5HM32-0AA0, 3-pole line protection, rated 25 A continuous, interrupting up to 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2125-5HM32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2125-5HM32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.0.6 W
3VA2125-5HM32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU330
Overcurrent protection functionLIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes
3VA2125-5HM32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2125-5HM32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2125-5HM32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2125-5HM32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

It carries a continuous current rating of 25 A across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling — and interrupts faults at 187 kA at 240 V, 121 kA at 415/440 V, and 75.6 kA at 500 V, with a 3.7 kA rating at 690 V. That interrupting capacity covers most industrial service-entrance and sub-feed applications without cascading upstream breakers.

Panel footprint and integration

The 3VA2125-5HM32-0AA0 measures 105 mm wide, 181 mm high, and 86 mm deep — a standard SENTRON 3VA footprint that fits existing 3VA cutouts and busbar systems. The 3-pole body accepts line-side lugs or plug-in bases common to the 3VA platform, so a panel already tooled for a 3VA frame accepts this unit without re-drilling gland plates or re-spacing DIN-rail assemblies.

Ground-fault monitoring variant

This order code includes a summation-current ground-fault monitoring function — the L-conductor summation method — which detects residual currents by summing the phase currents through a common core. It does not include undervoltage release, trip indicator, communication, or voltage-triggered functions, so if your BOM calls for those, this is the wrong variant.

Frequently asked questions

How do I get current pricing and availability for 3VA2125-5HM32-0AA0?

This MCCB is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

What is 3VA2125-5HM32-0AA0's interrupting capacity at 240 V?

It is rated 187 kA at 240 V, with 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V.

Does this MCCB include ground-fault monitoring?

Yes, it includes summation-current ground-fault monitoring on the L-conductor. It does not include undervoltage release or communication functions.

MPN
3VA2125-5HM32-0AA0