Skip to main content
Siemens 3VA2140-5MN32-0DL0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2140-5MN32-0DL0 MCCB, 40 A, 3-Pole, Motor

MPN3VA2140-5MN32-0DL0

Siemens SENTRON 3VA2140-5MN32-0DL0, 3-pole molded case circuit breaker, motor protection, 40 A rated, ETU350M trip unit, breaking capacity 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2140-5MN32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2140-5MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2140-5MN32-0DL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C38.4 A
Current at 60 °C37.6 A
Current at 65 °C36.8 A
Current at 70 °C36 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.75 W
3VA2140-5MN32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
3VA2140-5MN32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-5MN32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2140-5MN32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-5MN32-0DL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

40 A, 3-pole motor-protection MCCB with ETU350M trip unit

It carries a breaking capacity of 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — covering most industrial line-to-line fault levels up to the 690 V tier.

The 40 A rating is flat from 40 °C through 50 °C, then derates slightly to 38.4 A at 55 °C, 37.6 A at 60 °C, 36.8 A at 65 °C, and 36 A at 70 °C. For a panel that runs warm — say a 55 °C internal ambient — the breaker still holds 38.4 A continuous, so a 40 A motor FLA is fine as long as the actual load current stays under that derated ceiling.

The depth of 86 mm leaves clearance behind the door for wiring and auxiliary connections.

Frequently asked questions

What is the 3VA2140-5MN32-0DL0 used for?

It is a 3-pole molded case circuit breaker with motor protection profile, rated 40 A, designed to protect three-phase motor circuits against overload, short-circuit, and phase failure. It uses an ETU350M electronic trip unit.

What breaking capacity does the 3VA2140-5MN32-0DL0 have at 415 V?

At 415 V the breaking capacity is 121 kA. At 240 V it is 187 kA, at 440 V 121 kA, at 500 V 75.6 kA, and at 690 V 17 kA.

Where can I buy the 3VA2140-5MN32-0DL0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ to confirm current availability and pricing at quote time.

Does the 3VA2140-5MN32-0DL0 include an undervoltage release?

Yes, it includes an undervoltage release (UVR) as standard, plus a set of auxiliary contacts: 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch HQ.

MPN
3VA2140-5MN32-0DL0