Siemens 3VA2140-5MN32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-5MN32-0AD0 SENTRON MCCB, 40 A, 121 kA at 415

MPN3VA2140-5MN32-0AD0

Siemens SENTRON 3VA2140-5MN32-0AD0, molded case circuit breaker, motor protection design, 3-pole, 40 A rated current, 121 kA breaking capacity at 415 V, 86 x 105 x 181 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2140-5MN32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21405MN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2140-5MN32-0AD0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classE
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.1.6 W

Protection & Trip Unit

3VA2140-5MN32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2140-5MN32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2140-5MN32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2140-5MN32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2140-5MN32-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens 3VA2140-5MN32-0AD0 is a SENTRON molded case circuit breaker (MCCB) built for motor protection duty. It's a 3-pole unit rated 40 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Breaking capacity hits 121 kA at 415 V, which puts it in the high-interrupting class for industrial distribution panels feeding motor control centers.

What the ratings mean for fit

The 40 A rating is flat from 40 °C to 70 °C, so if you're stuffing this into a hot panel next to drives or transformers, you don't lose headroom. That's unusual for a compact MCCB — many competitors start derating above 40 °C. The 121 kA at 415 V means it can sit upstream of a group of motor starters without needing a current-limiting fuse ahead of it, as long as the available fault current at the panel doesn't exceed that figure. At 240 V it's rated 187 kA, so it handles utility-transformer secondary faults cleanly. Phase failure detection is built in — that's the motor protection variant's job: if one phase drops, the breaker trips before single-phasing cooks the winding. No undervoltage release, no shunt trip, no communication module on this order code; it's a straight thermal-magnetic motor protector with auxiliary switches (3 HQ aux switches included per). The basic switch inside is 3VA21405MN320AA0, so if you're swapping just the internal mechanism, that's the spare part number.

Dimensions and panel fit

Footprint is 105 mm wide, 181 mm tall, 86 mm deep. That's a standard SENTRON 3VA2 frame size — mounts on DIN rail or direct panel via screw terminals. The 105 mm width means it occupies three 35 mm module spaces if you're laying out a DIN-rail enclosure. Depth of 86 mm leaves room for rear-access cabling in a 200 mm deep enclosure without forcing a right-angle bend on the incoming lugs.

Power loss and thermal management

Maximum power loss is 1.6 W at rated load. That's low enough that you don't need forced ventilation in a typical panel — the heat rise from this breaker alone won't push the internal ambient past the 70 °C operating limit. Storage range is -40 °C to 80 °C, so it tolerates warehouse extremes without issue.

Frequently asked questions

What is 3VA2140-5MN32-0AD0's breaking capacity at 415 V?

121 kA at 415 V — that's the interrupting rating for a 3-phase fault at that voltage level.

Where can I buy 3VA2140-5MN32-0AD0?

Sourced and quoted to order against an RFQ through independent distribution — availability and current pricing confirmed at quote time.

Does 3VA2140-5MN32-0AD0 include phase failure protection?

Yes, phase failure detection is built into this motor protection variant — it trips on loss of any phase.