Skip to main content
Siemens 3VA2140-5MN32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-5MN32-0AE0 SENTRON MCCB, 40 A, 3-Pole, 187 k

MPN3VA2140-5MN32-0AE0

Siemens SENTRON 3VA2140-5MN32-0AE0, molded case circuit breaker, 3-pole, 40 A, motor protection version, ETU350M electronic trip unit, 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2140-5MN32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2140-5MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2140-5MN32-0AE0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C38.4 A
Current at 60 °C37.6 A
Current at 65 °C36.8 A
Current at 70 °C36 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.75 W
3VA2140-5MN32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
3VA2140-5MN32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-5MN32-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2140-5MN32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-5MN32-0AE0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Siemens 3VA2140-5MN32-0AE0 — 40 A SENTRON MCCB with ETU350M

It carries a breaking capacity of 187 kA at 240 V AC and 121 kA at 415 V and 440 V AC — figures that place it in the high-interrupting class, sized for fault currents typical at the main distribution board or large motor branch circuit. The breaker ships with four HQ auxiliary switches and no undervoltage or shunt release fitted, so those functions must be added externally if required.

Rated insulation voltage is 800 V, and the interrupting ratings step down across the voltage range: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. The 40 A continuous rating holds from 40 °C through 50 °C ambient; above that it derates to 38.4 A at 55 °C and 36 A at 70 °C (–). Mounted in a panel that runs warm — near other breakers or a transformer — factor that derate into the load calculation. Maximum power loss is 75 W. No trip indicator is fitted, so a blown breaker requires a multimeter or auxiliary contact feedback to confirm state.

Frequently asked questions

What is the breaking capacity of 3VA2140-5MN32-0AE0 at 415 V?

121 kA at 415 V AC, which is the same rating it carries at 440 V. At 240 V it reaches 187 kA.

Does this MCCB include phase failure protection?

Yes, phase failure detection is built into the ETU350M trip unit. It will trip on a lost phase — a key feature for motor branch circuits.

Where can I buy 3VA2140-5MN32-0AE0 and how is it quoted?

This part is sourced to order through independent distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time.

MPN
3VA2140-5MN32-0AE0