Skip to main content
Siemens 3VA2140-6HN42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-6HN42-0AA0 SENTRON MCCB, 40 A, 4-Pole, ETU35

MPN3VA2140-6HN42-0AA0
Active

Siemens SENTRON 3VA2140-6HN42-0AA0, molded case circuit breaker, 4-pole, 40 A continuous, ETU350 electronic trip unit, line protection design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2140-6HN42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2140-6HN42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.1.6 W
3VA2140-6HN42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2140-6HN42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-6HN42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2140-6HN42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-6HN42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2140-6HN42-0AA0 is a 4-pole molded case circuit breaker rated for 40 A continuous current, with no derating across its full ambient range from -25 °C to 70 °C — a flat thermal curve that simplifies panel design in warm enclosures. Its ETU350 electronic trip unit handles line-protection duty with a breaking capacity that starts at 242 kA at 240 V and steps down through 187 kA at 415/440 V, 121 kA at 500 V, to 3.7 kA at 690 V — the high SCCR at the lower voltages means it can serve as a main or branch breaker in high-fault panels without cascading upstream. The 86 mm depth, 140 mm width, and 181 mm height fit the standard SENTRON 3VA footprint, so it mounts into existing panel layouts sized for the series without re-drilling gland plates or re-routing bus bars.

Integration notes

Power loss is 1.6 W maximum, negligible for thermal budgeting inside a multi-breaker panel. Storage range of -40 °C to 80 °C covers shipping and warehouse extremes; the operating range of -25 °C to 70 °C matches the flat 40 A rating.

Frequently asked questions

What is the breaking capacity of 3VA2140-6HN42-0AA0 at 240 V?

242 kA at 240 V, stepping down to 187 kA at 415/440 V, 121 kA at 500 V, and 3.7 kA at 690 V.

Where can I buy 3VA2140-6HN42-0AA0?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

Will 3VA2140-6HN42-0AA0 drop into a panel specified for 3VA2116-5JP32-0AE0?

Both are SENTRON 3VA series breakers sharing the same 86 mm depth, 140 mm width, and 181 mm height footprint, so mechanical fit is identical — the difference is in the trip unit and rating, not the mounting.

MPN
3VA2140-6HN42-0AA0