Skip to main content
Siemens 3VA2140-6KP42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-6KP42-0AA0 SENTRON MCCB, 40 A, 4-Pole, 242 k

MPN3VA2140-6KP42-0AA0
Active

Siemens SENTRON 3VA2 molded case circuit breaker, 4-pole, 40 A rated continuous current (Iu), ETU850 electronic trip unit, breaking capacity 242 kA at 240 V AC, line protection version, current lifecycle.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2140-6KP42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2140-6KP42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.8 kA
Power loss, max.1.6 W
3VA2140-6KP42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
3VA2140-6KP42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-6KP42-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2140-6KP42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-6KP42-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

The Siemens 3VA2140-6KP42-0AA0 is a SENTRON molded case circuit breaker rated for 40 A continuous current (Iu) across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Four poles, line protection version, with the ETU850 electronic trip unit. Breaking capacity hits 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.8 kA at 690 V. That 242 kA figure at 240 V means it handles the highest available fault currents on a 240 V secondary without upstream coordination worries — it's sized for the worst-case short-circuit at the main distribution board. Communication function is built in — the ETU850 supports data exchange for power monitoring and trip-event logging. Power loss maxes at 1.6 W, negligible for panel thermal budgeting.

Dimensions are 181 mm high, 140 mm wide, 86 mm deep. The 140 mm width is a standard 4-pole MCCB footprint — it drops into the same mounting cutout as other SENTRON 3VA2 4-pole frames. Operating temperature range is -40 °C to 70 °C, storage from -40 °C to 80 °C — fine for unheated electrical rooms or outdoor cabinets with heaters.

Frequently asked questions

Where can I buy 3VA2140-6KP42-0AA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is the breaking capacity of 3VA2140-6KP42-0AA0 at 240 V?

242 kA at 240 V AC — that's the highest short-circuit rating in the 3VA2 line for this frame size, suitable for main distribution boards with high available fault current.

Does 3VA2140-6KP42-0AA0 have communication capability?

Yes, the ETU850 trip unit includes a communication function for power monitoring and event logging.

MPN
3VA2140-6KP42-0AA0