Siemens 3VA2140-6KP46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-6KP46-0AA0 SENTRON MCCB, 40 A, 4-Pole, ETU85

MPN3VA2140-6KP46-0AA0
Active

Siemens SENTRON 3VA2140-6KP46-0AA0, molded case circuit breaker, 4-pole, 40 A, ETU850 electronic trip unit, line protection design, breaking capacity 242 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2140-6KP46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2140-6KP46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.1.6 W

Protection & Trip Unit

3VA2140-6KP46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2140-6KP46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2140-6KP46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2140-6KP46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2140-6KP46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

What this MCCB delivers

The Siemens 3VA2140-6KP46-0AA0 is a SENTRON molded case circuit breaker rated 40 A continuous with a 4-pole configuration. It carries the ETU850 electronic trip unit and is designed for line protection. Breaking capacity reaches 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. That 242 kA at 240 V means it can safely interrupt very high fault currents typical at the service entrance or in large distribution panels without upstream cascading. The adjustable current range spans 60 A minimum to 480 A maximum, giving the integrator room to coordinate with downstream breakers. The 40 A continuous rating holds flat from 40 °C up to 70 °C (–), so no derating is needed in a warm enclosure — a practical advantage for a panel stuffed with heat-generating gear.

Panel fit and integration

Dimensions are 181 mm height, 140 mm width, and 86 mm depth. The 140 mm width is a standard 4-pole MCCB footprint; it fits existing SENTRON panel cutouts and busbar systems without modification. IP40 protection on the front means it's protected against tools and small wires entering the enclosure — standard for indoor panel mounting. No undervoltage release or ground-fault monitoring is built in, so those functions must be added externally if the application requires them.

MPN
3VA2140-6KP46-0AA0