Skip to main content
Siemens 3VA2140-7JP32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-7JP32-0AA0 MCCB, 40 A, 3-Pole, ETU550, 330 k

MPN3VA2140-7JP32-0AA0
Active

Siemens SENTRON 3VA2140-7JP32-0AA0, molded case circuit breaker, 3-pole, 40 A, ETU550 electronic trip unit, 330 kA at 240 V, line protection, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2140-7JP32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2140-7JP32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.1.6 W
3VA2140-7JP32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
3VA2140-7JP32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-7JP32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2140-7JP32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-7JP32-0AA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2140-7JP32-0AA0 is a 3-pole molded case circuit breaker rated 40 A continuous at ambient temperatures from 40 °C up to 70 °C with no derating — meaning it holds its full 40 A rating across the typical panel interior range, so you don't have to oversize for heat buildup inside the enclosure. The interrupting ratings climb to 330 kA at 240 V, 242 kA at 415 V and 440 V, and 187 kA at 500 V — numbers that place it in the high-fault-current class, suited for main or feeder positions where available fault current is substantial. At 690 V it still clears 3.7 kA.

Trip unit and protection logic

It uses the ETU550 electronic trip unit, which supports adjustable N-conductor protection (OFF, 40 % to 160 % of the phase setting) — useful for panels feeding unbalanced loads or where the neutral conductor needs its own pickup curve.

Listed as current production.

Communication and auxiliary options

The breaker includes a communication function — the ETU550 can interface with the SENTRON powerconfig software and support Modbus or PROFIBUS via a communication module, giving visibility into load current and trip events without a separate power meter.

Frequently asked questions

What is 3VA2140-7JP32-0AA0's depth?

The depth is 86 mm (3.39 in), which fits standard backpanel depths without a sub-panel extension.

Will 3VA2140-7JP32-0AA0 drop into a panel specified around 3VA2140-8JQ42-0AA0 without rewiring?

Both are 3-pole SENTRON 3VA frame breakers with the same physical footprint — 105 mm wide, 181 mm tall, 86 mm deep — so the mechanical swap is straightforward. The trip unit differs (ETU550 vs. the 8JQ42 variant's unit), so verify the protection curve matches your coordination study before committing the BOM line.

MPN
3VA2140-7JP32-0AA0