Siemens 3VA2163-0HN32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-0HN32-0AA0 SENTRON MCCB, 63 A, 440 kA at 415

MPN3VA2163-0HN32-0AA0
Active

Siemens SENTRON molded case circuit breaker, 3VA2163-0HN32-0AA0, 3-pole, 63 A rated continuous current, ETU350 electronic trip unit, 440 kA breaking capacity at 415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2163-0HN32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2163-0HN32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.3.1 W
3VA2163-0HN32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2163-0HN32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-0HN32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2163-0HN32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-0HN32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens 3VA2163-0HN32-0AA0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for 63 A continuous current with an ETU350 electronic trip unit. That 63 A holds flat across the full operating range from 40 °C to 70 °C — no derating curve to chase for a warm panel. The 440 kA breaking capacity at 415 V AC means it can interrupt fault currents up to that level without upstream coordination issues; at 690 V AC it still clears 187 kA. Insulation voltage is rated 800 V, so it handles 480 V and 600 V class systems with headroom. This is a straight feeder or main breaker for a distribution panel where the trip curve and selectivity come from the ETU350 settings, not auxiliary hardware.

DIN-rail integration and panel footprint

Mounts on standard DIN rail. Dimensions: 105 mm wide, 181 mm tall, 86 mm deep — the 86 mm depth (3.39 in) is the key number for gland-plate clearance and cover depth.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

440 kA at 415 V AC, and 187 kA at 690 V AC.

What trip unit does the 3VA2163-0HN32-0AA0 use?

ETU350 electronic trip unit — adjustable for coordination studies without swapping the breaker.

Does this MCCB include undervoltage release or ground-fault protection?

No undervoltage release and no ground-fault monitoring version. Line protection only.

Where can I buy the 3VA2163-0HN32-0AA0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN