Siemens 3VA2163-5HK46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-5HK46-0AA0 SENTRON MCCB, 63 A, 4-Pole, 187 k

MPN3VA2163-5HK46-0AA0
Active

Siemens SENTRON 3VA2 series molded case circuit breaker, 63 A, 4-pole, ETU340 electronic trip unit, 187 kA interrupting at 240 V AC, line protection version.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2163-5HK46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2163-5HK46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.4 W
3VA2163-5HK46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340
Overcurrent protection functionELISA LI
Ground-fault monitoringWithout
3VA2163-5HK46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-5HK46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2163-5HK46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-5HK46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

The Siemens 3VA2163-5HK46-0AA0 is a SENTRON 3VA2 molded case circuit breaker (MCCB) rated 63 A continuous at 40 °C through 70 °C — no derating needed across that band, which simplifies panel schedules in warm enclosures. Its interrupting capacity hits 187 kA at 240 V and 121 kA at 415 V, making it a fit for high-fault locations like transformer secondaries or large motor control centers where upstream breakers need full selectivity. Four poles with ETU340 electronic trip unit; N-conductor protection adjustable OFF or 100 %.

The case measures 140 mm wide by 181 mm tall by 86 mm deep — a standard 3VA2 footprint that drops into existing SENTRON panel cutouts and busbar systems without re-drilling the mounting plate.

Trip unit and protection features

Power loss is 4 W maximum at rated current. Ambient operating range -25 °C to 70 °C; storage range -40 °C to 80 °C.

Frequently asked questions

What is 3VA2163-5HK46-0AA0's listed depth (86 mm) on this component line?

The depth is 86 mm, with a width of 140 mm and height of 181 mm — a standard 3VA2 footprint.

Will 3VA2163-5HK46-0AA0 drop into a panel that was specified around 3VA2163-8HM32-0AA0 without rewiring?

Both are 3VA2-frame breakers sharing the same 140 x 181 x 86 mm envelope, so the mechanical fit is identical. The difference is in the trip unit and accessories — verify the ETU340 settings and any add-on modules match the original panel design before swapping.

MPN
3VA2163-5HK46-0AA0