Rated continuous current Iu is 200 A at 40 °C, and it holds that rating through 50 °C; above that it derates to 192 A at 55 °C, 188 A at 60 °C, 184 A at 65 °C, and 180 A at 70 °C. Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — figures that cover most industrial distribution panels with high fault current.
Max power loss is 75 W; plan ventilation accordingly if the enclosure is tightly packed.