Skip to main content
Siemens 3VA2220-5MN32-0AJ0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2220-5MN32-0AJ0 SENTRON MCCB, 200A, 187kA at 240V

MPN3VA2220-5MN32-0AJ0

Siemens SENTRON 3VA2220-5MN32-0AJ0, molded case circuit breaker, 3-pole, 200 A rated, motor protection version, ETU350M electronic trip unit, 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2220-5MN32-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2220-5MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2220-5MN32-0AJ0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C192 A
Current at 60 °C188 A
Current at 65 °C184 A
Current at 70 °C180 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.75 W
3VA2220-5MN32-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
3VA2220-5MN32-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2220-5MN32-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2220-5MN32-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2220-5MN32-0AJ0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

MCCB for motor protection — 200 A frame with ETU350M

The Siemens SENTRON 3VA2220-5MN32-0AJ0 is a 3-pole molded case circuit breaker rated for 200 A continuous current at 40 °C, with an ETU350M electronic trip unit configured for motor protection duty. The 200 A rating holds flat across 40–50 °C, then derates to 192 A at 55 °C, 188 A at 60 °C, 184 A at 65 °C, and 180 A at 70 °C (–) — useful for panels running near the thermal ceiling. Breaking capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V.

Front IP40 protection suits standard panel environments. The base switch variant is 3VA2220-5MN32-0AA0.

Maximum power loss is 75 W.

Frequently asked questions

What is the breaking capacity of 3VA2220-5MN32-0AJ0 at 415 V?

121 kA at 415 V, and the same 121 kA at 440 V. At 240 V it reaches 187 kA, at 500 V it is 75.6 kA, and at 690 V it is 17 kA.

What trip unit does this MCCB use?

The ETU350M electronic trip unit, designed for motor protection applications. Phase failure detection is included.

Where can I buy 3VA2220-5MN32-0AJ0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN
3VA2220-5MN32-0AJ0