Skip to main content
Siemens 3VA2440-5MN32-0AJ0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2440-5MN32-0AJ0 MCCB, 400A, 187kA at 240V

MPN3VA2440-5MN32-0AJ0

Siemens SENTRON 3VA2440-5MN32-0AJ0, molded case circuit breaker, 3-pole, motor protection version, 400 A rated continuous current, ETU350M electronic trip unit, 187 kA at 240 V, 121 kA at 415 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2440-5MN32-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2440-5MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2440-5MN32-0AJ0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C384 A
Current at 60 °C376 A
Current at 65 °C368 A
Current at 70 °C360 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.63.5 W
3VA2440-5MN32-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
3VA2440-5MN32-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2440-5MN32-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2440-5MN32-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2440-5MN32-0AJ0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

That 400 A holds flat from 40 °C up to 50 °C; above that it derates to 384 A at 55 °C, 376 A at 60 °C, 368 A at 65 °C, and 360 A at 70 °C — so if this lands in a hot panel near a drive or transformer, the 50 °C threshold is the one to watch. Breaking capacity runs 187 kA at 240 V, drops to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 17 kA at 690 V.

Motor protection build — what's inside and what's not

This is the motor protection version, meaning the ETU350M trip unit includes phase failure detection and a trip indicator. Power loss maxes at 63.5 W — that's the heat the breaker dumps into the enclosure. In a multi-breaker lineup, that figure drives the ventilation or derating calc for the surrounding units.

That 138 mm width for a 3-pole 400 A frame is standard for SENTRON 3VA — it fits the same mounting footprint as other breakers in the series, so swapping from a lower-rated unit doesn't require drilling new holes or reworking the bus bars. Keep it in a dry indoor panel. The storage low end matters if this sits in an unheated warehouse before installation.

Frequently asked questions

Does 3VA2440-5MN32-0AJ0 include phase failure detection?

Yes, the ETU350M trip unit includes phase failure detection as standard on this motor protection version.

What compliance documentation does Siemens provide for 3VA2440-5MN32-0AJ0?

As a current-production SENTRON MCCB, it carries the standard Siemens declarations (CE, UKCA, RoHS, REACH) available through the Siemens Industry Online Support portal. Specific certification details (UL, IEC) are part of the product documentation package — request them with your RFQ.

MPN
3VA2440-5MN32-0AJ0