Siemens 3VA2440-5HL32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2440-5HL32-0AD0 SENTRON MCCB, 400 A, 3-pole, ETU3

MPN3VA2440-5HL32-0AD0

Siemens SENTRON 3VA2440-5HL32-0AD0, molded case circuit breaker, 3-pole, 400 A, ETU320 electronic trip unit, line protection, 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2440-5HL32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2440-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2440-5HL32-0AD0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C384 A
Current at 60 °C376 A
Current at 65 °C368 A
Current at 70 °C360 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.63.5 W
3VA2440-5HL32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2440-5HL32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2440-5HL32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2440-5HL32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2440-5HL32-0AD0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The Siemens SENTRON 3VA2440-5HL32-0AD0 is a 3-pole molded case circuit breaker (MCCB) rated for 400 A continuous current at 40 °C, with an ETU320 electronic trip unit for line protection. It's the main disconnect and fault protection for a feeder or large motor branch in a 400 V panel — the kind of breaker you spec when you need adjustable thermal-magnetic or electronic curve shaping and a high interrupting rating.

Breaking capacity — what the voltage columns mean for your fault duty

This breaker carries 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. At 415 V, 121 kA covers most industrial service-entrance and large sub-feed applications without series-rating gymnastics.

Rated 400 A from 40 °C through 50 °C, then it steps down: 384 A at 55 °C, 376 A at 60 °C, 368 A at 65 °C, 360 A at 70 °C. Size your load and enclosure ventilation accordingly.

What's inside — trip unit and aux contacts

The basic switch is order code 3VA2440-5HL32-0AA0; the integrated auxiliary trip is 3VA9608-0BB24.

Panel fit — dimensions and environment

At 248 mm high, 138 mm wide, 110 mm deep, this is a standard 3VA2 frame — it bolts into the same footprint as other 3VA2 breakers. Max power loss is 63.5 W, so factor that into your enclosure thermal budget if you're packing multiple breakers in a closed cabinet.

Frequently asked questions

Where can I buy 3VA2440-5HL32-0AD0?

We source this breaker to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2440-5HL32-0AD0 at 415 V?

It's rated 121 kA at 415 V, which covers most industrial sub-feed applications.

Does 3VA2440-5HL32-0AD0 include a ground-fault trip?

No, this variant ships without ground-fault monitoring. The ETU320 release handles overload and short-circuit protection only.

MPN