Siemens SENTRON 3VA2440-7KP42-0AA0, Molded case circuit breaker, Line protection, 4-pole, 400 A, ETU850 electronic trip unit, breaking capacity 330 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2440-7KP42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2440-7KP42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C376 A
Current at 60 °C352 A
Current at 65 °C324 A
Current at 70 °C300 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V9 kA
Power loss, max.63.3 W
3VA2440-7KP42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
3VA2440-7KP42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2440-7KP42-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2440-7KP42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2440-7KP42-0AA0 — Mechanical
ParameterValue
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.8 in
Width (in)7.2 in
Depth (in)4.3 in

Product details

It uses the ETU850 electronic trip unit. Breaking capacity is the headline number here: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 9 kA at 690 V. It also carries communication and other measurement functions onboard, meaning it can report status and metering data back to a controller — useful for a panel that needs load monitoring without a separate power meter. The N-conductor protection is adjustable from OFF to 20% up to 130%, so it handles 4-wire systems with neutral protection as needed.

Dimensions: 248 mm high, 184 mm wide, 110 mm deep. Power loss is 63.3 W maximum at rated current.

The ETU850 trip unit allows fine-tuning of the long-time pickup, short-time pickup, and instantaneous settings.