Skip to main content
Siemens 3VA2612-6HN42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2612-6HN42-0AA0 SENTRON MCCB, 1250 A, H Class, 4-

MPN3VA2612-6HN42-0AA0
Active

Siemens SENTRON 3VA2 series molded case circuit breaker, 3VA2612-6HN42-0AA0, 4-pole, 1250 A continuous, H switching capacity class, ETU350 LSI electronic trip unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2612-6HN42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2612-6HN42-0AA0 — Ratings
ParameterValue
Number of poles4
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V73.5 kA
Power loss, max.516 W
3VA2612-6HN42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
3VA2612-6HN42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeboth sides processed busbar connection piece
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2612-6HN42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA2612-6HN42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2612-6HN42-0AA0 — Mechanical
ParameterValue
Height320 mm
Width280 mm
Depth120 mm
Height (in)12.6 in
Width (in)11.02 in
Depth (in)4.72 in

Product details

The Siemens 3VA2612-6HN42-0AA0 is a SENTRON 3VA2 molded case circuit breaker rated for 1250 A continuous current (Iu) with an H switching capacity class, meaning it handles high fault currents across common industrial voltages: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 73.5 kA at 690 V. This makes it suitable for main feeder or large motor protection in 400 V-class distribution where high SCCR is needed to avoid cascading failures upstream. The ETU350 electronic trip unit provides LSI protection (long-time, short-time, instantaneous) with adjustable settings, including a fixed instantaneous pickup at 12 500 A (10× In). The 4-pole design includes adjustable neutral protection (OFF, 50%, 100%). Front IP40 rating suits panel-mount indoor use; the 120 mm depth fits standard 3VA2 switchboard form factors.

Frequently asked questions

How do I get current pricing and availability for 3VA2612-6HN42-0AA0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; we source through independent distribution and quote to order.

What is 3VA2612-6HN42-0AA0's breaking capacity at 415 V?

187 kA at 415 V, same as at 440 V. At 240 V it reaches 242 kA.

What trip unit does this MCCB use?

The ETU350 electronic trip unit with LSI protection (long-time, short-time, instantaneous). Instantaneous pickup is fixed at 12 500 A.

Will 3VA2612-6HN42-0AA0 drop into a panel specified around 3VA2110-7HK42-0AA0 without rewiring?

No — the 3VA2612-6HN42-0AA0 is a 1250 A 4-pole frame with H capacity, while the 3VA2110-7HK42-0AA0 is a different frame size and rating. Panel cutouts, bus connections, and wiring will differ; verify mechanical fit and electrical coordination before substitution.

MPN
3VA2612-6HN42-0AA0