Overload protection is adjustable Ir=500A...1250A, short-circuit protection Ii=1.5...10 x In, and ground-fault protection Ig=0.2...1 x In with a time delay tg=0.1/0.3s. The N conductor protection is adjustable (OFF, up to 100%).
Deployment context
This breaker mounts in a fixed or withdrawable chassis within a 3VA2 switchboard or panel. The 4-pole configuration suits three-phase four-wire systems (TN-S or TN-C-S) where neutral protection and ground-fault detection are required. The ETU330 LIG unit provides LSIG protection — long-time, short-time, instantaneous, and ground-fault — covering cable, busbar, and feeder protection in one device.