Skip to main content
Siemens 3VM1040-4ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1040-4ED32-0AA0 SENTRON MCCB, 400 A, 3-Pole, Line

MPN3VM1040-4ED32-0AA0
Active

Siemens SENTRON 3VM1040-4ED32-0AA0, molded case circuit breaker, 3-pole, 400 A, TM210 overcurrent release, line protection design, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1040-4ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VM1040-4ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C39 A
Current at 60 °C39 A
Current at 65 °C38 A
Current at 70 °C37 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Breaking capacity at 440 V40 kA
Breaking capacity at 500 V12 kA
Power loss, max.14 W
3VM1040-4ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VM1040-4ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1040-4ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1040-4ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1040-4ED32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.12 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

This is the breaker you spec into a main feeder or heavy branch circuit where you need a single interrupting device that can handle the full load and clear faults fast. The TM210 overcurrent release means it uses a thermal-magnetic trip — thermal for overloads, magnetic for short-circuits — no electronic adjustments, no communication module, just a straightforward, field-reliable trip curve. The IP40 front protection keeps tools and fingers out of the live terminals but isn't rated for washdown — this lives inside a dry enclosure.

At 240 V, the interrupting rating is 121 kA. That drops to 76 kA at 415 V, 40 kA at 440 V, and 12 kA at 500 V. The 12 kA at 500 V is the limiting case; don't put this on a 500 V bus with more than 12 kA available unless you've got a current-limiting upstream device.

Thermal Derating — Don't Ignore the Cabinet Temperature

At 55 °C it's 39 A, at 60 °C it's 39 A, at 65 °C it's 38 A, and at 70 °C it's 37 A. If your panel ambient runs 65 °C (tight enclosure, solar load, next to a furnace line), you lose 3 A from the nameplate. That's a 7.5% reduction — enough to nuisance-trip if you sized the load right at 40 A. Always size the breaker for the actual cabinet temperature, not the 40 °C rating.

Depth is 70 mm, width is 76.2 mm, height is 130 mm. That's a compact footprint for a 400 A frame — it fits standard distribution panel gutters without crowding the bend radius on incoming cables. The 3-pole block takes up about 3 inches of rail space.

Frequently asked questions

Where can I buy 3VM1040-4ED32-0AA0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the latest lead time and price.

What is the breaking capacity of 3VM1040-4ED32-0AA0 at 240 V?

At 240 V, the interrupting rating is 121 kA. At 415 V it's 76 kA, at 440 V it's 40 kA, and at 500 V it's 12 kA.

What is the depth of 3VM1040-4ED32-0AA0?

The depth is 70 mm (2.76 inches). Width is 76.2 mm (3 inches), height is 130 mm (5.12 inches).

Will 3VM1040-4ED32-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0?

The 3VM1040 is a different frame series than the 3VA1110 — the 3VA series uses electronic trip units and has different mounting dimensions and accessory compatibility. Mechanical fit is not guaranteed without checking the panel cutout and bus bar spacing against the 70 mm depth and 76.2 mm width of the 3VM.

MPN