SENTRON 3VM1020-4ED32-0AA0 — 20 A MCCB with TM210 Trip Unit
The Siemens 3VM1020-4ED32-0AA0 is a current-production SENTRON molded case circuit breaker (MCCB) in a 3-pole configuration, rated 20 A continuous at 40 °C ambient with a TM210 thermal-magnetic overcurrent release. Its breaking capacity reaches 121 kA at 240 V AC, 76 kA at 415 V, 40 kA at 440 V, and 12 kA at 500 V — figures that cover most industrial distribution and motor branch-circuit fault levels without cascading upstream.
Thermal Derating and Application Limits
The 3VM1020-4ED32-0AA0 holds its full 20 A rating from 40 °C through 55 °C, then derates to 19 A at 60–65 °C and 18 A at 70 °C.
Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint that drops into most DIN-rail or panel-mount enclosures without re-drilling.