Skip to main content
Siemens 3VM1116-3GD42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1116-3GD42-0AA0 SENTRON MCCB, 160 A, 4-Pole, 76 k

MPN3VM1116-3GD42-0AA0
Active

Siemens SENTRON 3VM1116-3GD42-0AA0, molded case circuit breaker, 4-pole, 160 A rated continuous current, TM210 thermal-magnetic release, breaking capacity 76 kA at 240 V AC, 53 kA at 415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1116-3GD42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1116-3GD42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Power loss, max.38 W
3VM1116-3GD42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1116-3GD42-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1116-3GD42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1116-3GD42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1116-3GD42-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.1 in
Width (in)4 in
Depth (in)2.8 in

Product details

SENTRON 3VM1116-3GD42-0AA0 — 160 A Line Protection MCCB

Its TM210 thermal-magnetic release provides fixed instantaneous and adjustable thermal protection, sized for the full 160 A rating — no derating needed at 40 °C, 45 °C, or 50 °C, where it holds the full 160 A. Breaking capacity runs 76 kA at 240 V AC, 53 kA at 415 V AC, and 32 kA at 440 V AC — enough for high-fault utility feeds without cascading upstream breakers.

Thermal Performance and Panel Fit

Dimensions are 70 mm deep, 101.6 mm wide, and 130 mm high — a compact 4-pole footprint that fits standard Siemens SENTRON distribution panel mounting. At 55 °C the breaker still carries 158 A, dropping to 150 A at 70 °C; the thermal curve means you can pack it into a warm enclosure without oversizing the frame. Maximum power loss is 38 W — factor that into enclosure ventilation when grouping several breakers.

No direct functional replacement is needed at this lifecycle stage — the part is the active release.

Frequently asked questions

Does this breaker have a communication function?

No — the 3VM1116-3GD42-0AA0 is a standalone line protection MCCB without integrated communication.

MPN