Siemens 3VM1125-4ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VM1125-4ED32-0AA0 MCCB, 3-pole, 25 A, 121 kA at 240

MPN3VM1125-4ED32-0AA0
Active

SENTRON 3VM1125-4ED32-0AA0, molded case circuit breaker, 3-pole, 25 A, interrupting 121 kA at 240 V AC, 76.2 mm wide, 130 mm tall, 70 mm deep.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1125-4ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1125-4ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Breaking capacity at 440 V53 kA
Breaking capacity at 500 V11.9 kA
Power loss, max.8.5 W
3VM1125-4ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VM1125-4ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1125-4ED32-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1125-4ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1125-4ED32-0AA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.1 in
Width (in)3 in
Depth (in)2.8 in

Product details

The SENTRON 3VM1125-4ED32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 25 A continuous current at 40 °C, with a TM210 thermal-magnetic release. Its interrupting capacity hits 121 kA at 240 V AC — enough to handle high-fault utility feeds without cascading upstream — and still clears 76 kA at 415 V, 53 kA at 440 V, and 11.9 kA at 500 V. That SCCR headroom makes it a solid choice for main or branch protection in panels where fault current is known to be high.

Above that it derates gently: 24 A at 55 °C and 60 °C, then 23 A at 65 °C and 70 °C.

At 76.2 mm wide, 130 mm tall, and 70 mm deep, this MCCB fits standard panel-mount cutouts for 3-pole SENTRON frames.

Frequently asked questions

Where can I buy 3VM1125-4ED32-0AA0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price.

What are the key interrupting ratings for 3VM1125-4ED32-0AA0?

It interrupts 121 kA at 240 V AC, 76 kA at 415 V, 53 kA at 440 V, and 11.9 kA at 500 V. These ratings let it clear high-fault line-side faults without requiring an upstream current-limiting fuse.

Will 3VM1125-4ED32-0AA0 drop into a panel designed for 3VA2025-8HN42-0AA0?

The 3VM1125-4ED32-0AA0 is a different frame generation from the 3VA series — physical dimensions and mounting centres may differ. Verify the cutout dimensions (76.2 mm wide, 130 mm tall) against your panel layout before substituting.

MPN