Siemens SENTRON 3VM1225-4ED32-0AA0 — 250 A MCCB, TM210 Release
The interrupting ratings are what decide fit: 121 kA at 240 V, 76 kA at 415 V, 53 kA at 440 V, and 17 kA at 500 V — so at 415 V it clears faults up to 76 kA without cascading upstream, which is the figure most panel builders check for IEC 60947-2 coordination.
Thermal Derating and Continuous Current
Above that it derates linearly: 243.3 A at 55 °C, 236.5 A at 60 °C, 229.8 A at 65 °C, and 223 A at 70 °C. If the panel ambient hits 60 °C, the available continuous current drops to 236.5 A — the so-what is that a 250 A feeder needs a panel ventilation review or a higher-frame breaker if the enclosure runs hot.
Physical Integration and Approvals
The TM210 release design means the thermal and magnetic settings are factory-fixed; no field-adjustable dials.