It carries a continuous current of 32 A at 40 °C and holds that rating up to 50 °C; at 55 °C it derates to 31 A, and at 70 °C to 30 A. The interrupting capacity hits 76 kA at 240 V AC, 53 kA at 415 V, 32 kA at 440 V, and 12 kA at 500 V — so the available fault current at the panel dictates which voltage column you use for sizing.
Three-pole construction means it occupies a single 76.2 mm wide slot in the distribution board — standard for a 32 A MCCB in a SENTRON panel.