Skip to main content
Siemens 3VM1116-3EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1116-3EE32-0AA0 SENTRON MCCB, 160 A, 3-Pole, 76 k

MPN3VM1116-3EE32-0AA0
Active

Siemens SENTRON 3VM1116-3EE32-0AA0, molded case circuit breaker, 3-pole, 160 A, TM220 release, 76 kA at 240 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VM1116-3EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VM1116-3EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V12 kA
Power loss, max.38 W

Protection & Trip Unit

3VM1116-3EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VM1116-3EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40

Accessories & Functions

3VM1116-3EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VM1116-3EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VM1116-3EE32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens SENTRON 3VM1116-3EE32-0AA0 — 160 A MCCB, TM220 Release

The Siemens 3VM1116-3EE32-0AA0 is a 3-pole molded case circuit breaker from the SENTRON line, rated 160 A continuous at 40 °C and designed for line protection. The TM220 thermal-magnetic release provides overload and short-circuit protection without undervoltage or ground-fault monitoring. Breaking capacity hits 76 kA at 240 V, 53 kA at 415 V, and 32 kA at 440 V — enough headroom for most industrial secondary-distribution panels. The front face carries IP40 protection, so it's suited for enclosed panel mounting where tools or fingers won't contact live parts.

Thermal Derating and Ambient Range

Full 160 A rating holds from 40 °C through 50 °C. At 55 °C it derates to 158 A, at 60 °C to 155 A, at 65 °C to 153 A, and at 70 °C to 150 A. Operating ambient spans -25 °C to 70 °C; storage range is -40 °C to 80 °C. Maximum power loss is 38 W. If the panel runs hot — say a packed enclosure near a furnace line — the 150 A floor at 70 °C still covers most 150 A feeder circuits without upsizing.

Physical Fit and Panel Integration

Dimensions: 130 mm height, 76.2 mm width, 70 mm depth. The 3-pole footprint is standard for SENTRON 3VM frames — no surprises on the DIN rail or mounting plate. No communication module, no undervoltage release, no ground-fault monitoring; it's a straight thermal-magnetic breaker. If your BOM calls for a bare MCCB with no auxiliaries, this is the clean drop-in.

Frequently asked questions

What is the breaking capacity of 3VM1116-3EE32-0AA0 at 240 V?

76 kA at 240 V, 53 kA at 415 V, 32 kA at 440 V, and 12 kA at 500 V.

Where can I buy 3VM1116-3EE32-0AA0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
3VM1116-3EE32-0AA0