Skip to main content
Siemens 3VM1150-4ED22-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1150-4ED22-0AA0 SENTRON MCCB, 2-Pole, 50A, 121kA/

MPN3VM1150-4ED22-0AA0
Active

Siemens SENTRON 3VM1150-4ED22-0AA0, 2-pole molded case circuit breaker, line protection, TM210 release, 50 A (40 °C), 121 kA at 240 V AC, 76 kA at 415 V AC, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1150-4ED22-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1150-4ED22-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Power loss, max.10 W
3VM1150-4ED22-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1150-4ED22-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1150-4ED22-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1150-4ED22-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1150-4ED22-0AA0 — Mechanical
ParameterValue
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.12 in
Width (in)2 in
Depth (in)2.76 in

Product details

It carries a 50 A continuous rating at 40 °C and holds that current flat through 50 °C — only dropping to 49 A at 55 °C and 45 A at 70 °C, so you don't lose headroom just because the panel runs warm.

That's a high-fault rating for a 50 A frame — it can clear a bolted fault on a large transformer secondary without upstream fuses having to coordinate. The 2-pole format means it fits single-phase or DC circuits up to 250 V DC, and the IP40 front keeps dust and accidental contact out of the enclosure face.

Dimensions are 70 mm deep, 50.8 mm wide, 130 mm tall — the 2-pole width (about 2 inches) slots into a standard MCCB footprint.

Frequently asked questions

Where can I buy 3VM1150-4ED22-0AA0 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the interrupting capacity of 3VM1150-4ED22-0AA0?

121 kA at 240 V AC and 76 kA at 415 V AC — high enough for most secondary-side fault scenarios without upstream coordination.

Does 3VM1150-4ED22-0AA0 drop into a panel designed for 3VA1110-5EF36-0AD0?

Both are 2-pole Siemens MCCBs in the SENTRON family, but the 3VA series has different dimensions and release options; verify mounting hole pattern and bus-bar spacing before substituting.

MPN
3VM1150-4ED22-0AA0