Siemens SENTRON 3VM1220-4EE32-0AA0 — 200 A MCCB, Line Protection, Active Production
Breaking capacity is the headline here: 121 kA at 240 V AC, 76 kA at 415 V, 53 kA at 440 V, and 17 kA at 500 V. The TM220 release is a thermal-magnetic design — thermal element for overload, magnetic for short-circuit. That keeps it simple and reliable for basic line protection where you don't need adjustable curves or remote monitoring.
The current derating curve above 55 °C is published: 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, 176 A at 70 °C.