Siemens 3VM1225-4EE32-0AA0 — SENTRON MCCB, 250 A, Line Protection
It carries a maximum of 2 500 A and delivers a breaking capacity of 121 kA at 240 V AC, 76 kA at 415 V AC, 53 kA at 440 V AC, and 17 kA at 500 V AC — figures that tell you the fault current it can safely interrupt at each voltage level without upstream cascading. Current rating holds at 250 A up to 50 °C ambient, then derates to 243.3 A at 55 °C, 236.5 A at 60 °C, 229.8 A at 65 °C, and 223 A at 70 °C. Dimensions: 70 mm deep, 105 mm wide, 158 mm high.