Skip to main content
Siemens 3VM1332-5ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1332-5ED32-0AA0 SENTRON MCCB, 320 A, 3-Pole, 187

MPN3VM1332-5ED32-0AA0
Active

Siemens SENTRON 3VM1332-5ED32-0AA0, molded case circuit breaker, 3-pole, 320 A, TM210 thermal-magnetic release, line protection, 187 kA at 240 V, 121 kA at 415 V, 76 kA at 500 V, IP40 front, 110 x 138 x 248 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1332-5ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1332-5ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Current at 40 °C320 A
Current at 45 °C320 A
Current at 50 °C320 A
Current at 55 °C313 A
Current at 60 °C306 A
Current at 65 °C299 A
Current at 70 °C292 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V76 kA
Power loss, max.80 W
3VM1332-5ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1332-5ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1332-5ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1332-5ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1332-5ED32-0AA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

MCCB for high-fault panel protection

The Siemens SENTRON 3VM1332-5ED32-0AA0 is a 3-pole molded case circuit breaker rated for line protection, with a TM210 thermal-magnetic release and a continuous current of 320 A at 40 °C through 50 °C, derating to 292 A at 70 °C. Its interrupting capacity reaches 187 kA at 240 V AC, 121 kA at 415 V and 440 V AC, and 76 kA at 500 V AC — figures that place it in the high-fault tier for main or feeder breakers in industrial switchboards where available fault current exceeds 100 kA. Rated insulation voltage 800 V; max operating voltage 690 V AC or 500 V DC.

The 320 A rating holds flat from 40 °C to 50 °C ambient; above that it drops 1.4 A per degree, reaching 292 A at 70 °C. For a panel that runs at 55 °C, the usable current is 313 A — a 2.2 % reduction that may affect coordination with downstream devices.

Frequently asked questions

What is 3VM1332-5ED32-0AA0's listed depth (110 mm) on this component line?

The depth is 110 mm (4.33 in), with a width of 138 mm (5.43 in) and a height of 248 mm (9.76 in).

Will 3VM1332-5ED32-0AA0 drop into a panel that was specified around 3VA2225-5HN42-0BB0 without rewiring?

The 3VM1332-5ED32-0AA0 is a 3-pole 320 A MCCB with a TM210 release, while the 3VA2225-5HN42-0BB0 is a different frame size and rating; panel fit and bus-bar spacing should be verified against the specific cutout dimensions and mounting pattern before assuming interchangeability.

MPN
3VM1332-5ED32-0AA0