Specifications

3VM1332-4ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VM1332-4ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C320 A
Current at 45 °C320 A
Current at 50 °C320 A
Current at 55 °C313 A
Current at 60 °C306 A
Current at 65 °C299 A
Current at 70 °C292 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Breaking capacity at 440 V76 kA
Breaking capacity at 500 V53 kA
Power loss, max.80 W
3VM1332-4ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VM1332-4ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1332-4ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1332-4ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1332-4ED32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

Its TM210 thermal-magnetic release provides fixed overload and short-circuit protection, with a maximum breaking capacity of 121 kA at 240 V AC and 76 kA at 415 V AC — sufficient for high-fault utility feeds and large motor branch circuits.

Continuous current holds flat at 320 A from 40 °C through 50 °C, then derates to 292 A at 70 °C — meaning the breaker can be applied near its nameplate rating in most ventilated enclosures without oversizing.

The breaker measures 138 mm wide, 248 mm tall, and 110 mm deep — a 3-pole frame that fits standard switchboard and panelboard mounting patterns without special adapters. Front face carries an IP40 protection rating, suitable for general indoor panel environments where tools or fingers won't contact live parts. Maximum power dissipation is 80 W at rated load, so panel thermal calculations should account for that heat — particularly in sealed or compact enclosures.

Frequently asked questions

What type of overcurrent release does this MCCB use?

It uses a TM210 thermal-magnetic release — fixed thermal and magnetic trip settings, no electronic adjustment.

MPN
3VM1332-4ED32-0AA0