That makes it a straightforward, no-frills feeder breaker for fixed-load or lightly coordinated branches. Rated 32 A continuously at 40 °C ambient, it holds that same 32 A up to 50 °C, then derates gently to 30 A at 70 °C — useful when the breaker sits in a warm enclosure near other heat sources. The interrupting capacity tells the real story: 53 kA at 240 V AC, 32 kA at 415 V, 14 kA at 440 V, and 8 kA at 500 V. At 415 V the 32 kA covers most industrial panelboards; at 500 V the 8 kA still clears a moderate fault but you'd want to check selectivity with the upstream device. Physical footprint: 70 mm deep, 76.2 mm wide, 130 mm high — a compact 3-pole MCCB that fits standard DIN-rail or panel-mount enclosures.
Siemens SENTRON 3VM1032-2ED32-0AA0 MCCB, 3P, 32 A, 53 kA at
Siemens SENTRON 3VM1032-2ED32-0AA0, 3-pole molded case circuit breaker, 32 A at 40 °C, TM210 thermal-magnetic release, 53 kA at 240 V, line protection design.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 32 A |
| Current at 45 °C | 32 A |
| Current at 50 °C | 32 A |
| Current at 55 °C | 31 A |
| Current at 60 °C | 31 A |
| Current at 65 °C | 30 A |
| Current at 70 °C | 30 A |
| Switching capacity class | C |
| Breaking capacity at 240 V | 53 kA |
| Breaking capacity at 415 V | 32 kA |
| Breaking capacity at 440 V | 14 kA |
| Breaking capacity at 500 V | 8 kA |
| Power loss, max. | 11 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM210 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | nut keeper kit on both ends |
| Main circuit connector arrangement | Front connection |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | No |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 12 000 |
| Height | 130 mm |
| Width | 76.2 mm |
| Depth | 70 mm |
| Height (in) | 5.12 in |
| Width (in) | 3 in |
| Depth (in) | 2.76 in |
Product details
Frequently asked questions
Where can I buy 3VM1032-2ED32-0AA0 and get a price?
This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.
What is the closest functional second-source to 3VM1032-2ED32-0AA0?
The 3VA1110-5ED32-0AA0 is the closest peer — same poles, same 32 A rating, same thermal-magnetic release. The 3VA platform supports accessories (shunt trip, undervoltage release) that the 3VM lacks. Physically they share the same DIN-rail footprint and busbar system.
Will 3VM1032-2ED32-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0?
Yes, it will physically fit the same DIN rail and busbar system. The 3VM lacks accessory slots, so if your panel uses shunt trips or auxiliary contacts from the 3VA family, those won't transfer. For a straight feeder breaker it's a drop-in replacement.
What compliance documentation does this breaker come with?
The manufacturer provides RoHS, REACH, UL, and IEC declarations of conformity for the 3VM series. CE and UKCA markings are covered. Documentation ships with the order.