Skip to main content
Siemens 5SL4402-0RC — 4-Pole MCB (DIN Rail)

Siemens Betagard 5SL4402-0RC MCB, 2A 4P Z-Curve, 10kA

MPN5SL4402-0RC

Siemens Betagard 5SL4402-0RC, miniature circuit breaker, 2 A, 4-pole, Z characteristic, 10 kA breaking capacity per EN 60898, 15 kA per IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4402-0RC — Identification
ParameterValue
Brand nameBetagard
5SL4402-0RC — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated voltage, AC (multi-phase)440 V
5SL4402-0RC — Protection
ParameterValue
Tripping characteristic (trip curve)Z
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
5SL4402-0RC — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SL4402-0RC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

Z-curve MCB for sensitive and semiconductor loads

The Z curve operates between 2.5× and 4× In, meaning it clears short-circuits faster than a B-curve device at the same rating — critical for protecting thyristors, rectifiers, and PLC power supplies where fault energy must be limited quickly. Rated 415 V AC, 50/60 Hz, it fits into standard DIN-rail distribution boards as a 4-module-width unit (72 mm wide).

Rated breaking capacity is 10 kA per EN 60898 and 15 kA per IEC 60947-2 — the higher IEC figure applies when the breaker is used in industrial panels where prospective fault current can exceed 10 kA. The 15 kA rating at 415 V AC gives selectivity headroom downstream of a larger upstream device; you can coordinate this 2 A Z-curve with a 63 A or 100 A upstream MCB without losing discrimination.

Snap-on DIN-rail mount, 72 mm wide (4 MW), 76 mm deep, 90 mm tall, with 70 mm installation depth behind the panel surface. Mounting position is any — vertical, horizontal, or flat — so it fits tight enclosures without derating. IP20 with connected conductors; sealable cover option is available for tamper-proofing in public-access distribution boards.

Environmental and compliance range

Vibration rated at 50 m/s² from 25 to 150 Hz per IEC 60068-2-6, suitable for machine-mounted panels on conveyors or compressors.

Frequently asked questions

Where can I buy 5SL4402-0RC and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.

What is the difference between 5SL4402-0RC and the 5SL4363-7?

The 5SL4363-7 is a 3-pole C-curve MCB (SENTRON brand) while the 5SL4402-0RC is a 4-pole Z-curve (Betagard brand). The Z curve trips faster on low-level faults, making the 5SL4402-0RC the correct choice for semiconductor protection; the 5SL4363-7 is a general-purpose C-curve device for standard circuits. They are not drop-in substitutes — pole count and tripping characteristic differ.

What is 5SL4402-0RC's depth and width for panel layout?

Depth is 76 mm, width is 72 mm (4 modular width units), height is 90 mm, with 70 mm installation depth behind the panel.

What compliance documentation does this MCB carry?

The 5SL4402-0RC is rated per EN 60898 (10 kA) and IEC 60947-2 (15 kA), overvoltage category III, pollution degree 3. It is halogen-free and silicon-free. Specific UL/CSA or RoHS/REACH declarations should be requested at quote time as they are not listed in the spec record.

MPN