Siemens SENTRON RCD-unit, 3-pole, 63 A at AC, 300 mA Type A residual current, 50 Hz, IP20 with distribution board installed, 3 MW, 70 mm depth, 107 mm width, 90 mm height.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SM2635-6 — Electrical Ratings
ParameterValue
Number of poles3
Overvoltage categoryIII
5SM2635-6 — Identification
ParameterValue
Product designationRCD-unit
Product design / constructioninstantaneous
5SM2635-6 — Mechanical
ParameterValue
Mounting positionany
Width in modular units3
Maximum75 °C
Minimum-40 °C
Width107 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SM2635-6 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

It operates at 50 Hz and carries an insulation voltage (Ui) of 460 V. The 300 mA sensitivity means it's sized for whole-circuit earth-leakage protection rather than individual equipment; Type A handles pulsating DC fault currents that a plain AC type would miss.

At 40 °C the unit carries 58.6 A; at 55 °C it's 54.81 A; at 70 °C it drops to 50.4 A. The body is 3 modular-width units wide (107 mm), 70 mm deep, 90 mm tall, and mounts in any position. IP20 only when the distribution board is installed with connected conductors — not a standalone open-panel part.

Surge current resistance is 1 kA. No UL, CSA, or CE marks are listed in the spec record — verify local acceptance before specifying into a UL 508A panel.

Frequently asked questions

Where can I buy 5SM2635-6 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 5SM2635-6's listed depth and width?

Depth is 70 mm, width is 107 mm (3 modular-width units), height is 90 mm.

What residual current type and sensitivity does 5SM2635-6 use?

Type A residual current detection with a 300 mA rated fault current — suitable for pulsating DC fault currents from electronics or variable-speed drives.