The Siemens 5SM3322-4 is a SENTRON residual current operated circuit breaker (RCCB), 2-pole, Type B, short-time delayed, rated 25 A with a 30 mA trip sensitivity at 230 V AC. It's a current-production part, still in the active catalog. Type B residual current detection means it handles smooth DC, pulsating DC, and AC fault currents — the full spectrum you get from VFDs, UPS systems, and EV charging circuits. The short-time delayed design (3 kA surge current resistance) prevents nuisance tripping from transient surges or lightning-induced spikes. Overvoltage Category III suits it for fixed-installation distribution boards, not just socket outlets.
Snaps onto standard DIN rail (REG), any mounting position. Depth is 70 mm, matching the installation depth; no extra clearance needed behind the rail for the body.