Skip to main content
Siemens 5SM3312-3 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM3312-3 SENTRON RCCB, 25 A, 30 mA, Type F, 2-pole

MPN5SM3312-3

Siemens SENTRON 5SM3312-3 RCCB, 2-pole, Type F, short-time delayed, In: 25 A, 30 mA, Un AC: 230 V, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SM3312-3 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SM3312-3 — Identification
ParameterValue
Product designationRCCB
Product design / constructionShort-time delayed
5SM3312-3 — Mechanical
ParameterValue
Mounting positionany
Maximum45 °C
Minimum-25 °C
Installation depth70 mm
5SM3312-3 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SM3312-3 is a 2-pole SENTRON residual current circuit breaker (RCCB) rated 25 A at 230 V AC, with a 30 mA trip threshold and Type F fault-current discrimination. It is short-time delayed, meaning it withstands brief surge currents up to 3 kA without nuisance tripping — useful on circuits feeding switched-mode power supplies or drives that produce mixed-frequency leakage.

Rating and derating across ambient temperature

Full rated current of 25 A is maintained up to 45 °C ambient. Above that, derating applies: 23.5 A at 50 °C, 22 A at 55 °C, 20.5 A at 60 °C, 19 A at 65 °C, and 17.5 A at 70 °C. The maximum permissible ambient is 75 °C; minimum is -40 °C.

Type F fault current and short-time delay

The short-time delayed switching function (3 kA surge current resistance) prevents false trips from transient surges — common on motor-start or capacitor-switching events. Rated short-circuit current is 10 kA.

Installation depth is 70 mm. Mounting position is any orientation. IP20 protection with connected conductors in a distribution board. Finger and back-of-hand safe per the shock protection class.

Frequently asked questions

What is 5SM3312-3 used for?

It is a 2-pole Type F RCCB (residual current circuit breaker) rated 25 A, 30 mA, 230 V AC, short-time delayed. It protects against AC and pulsating DC fault currents, especially on circuits with variable-speed drives or frequency converters.

What are the key ratings of 5SM3312-3?

Rated current 25 A, rated voltage 230 V AC, tripping residual current 30 mA, short-circuit current rating 10 kA, surge current resistance 3 kA, Type F fault current, short-time delayed design.

Where can I buy 5SM3312-3?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

Will 5SM3312-3 drop into a panel specified around 5SY4304-7CV without rewiring?

No — the 5SY4304-7CV is a miniature circuit breaker (MCB), not an RCCB. They serve different protection functions and are not drop-in interchangeable. The 5SM3312-3 is an RCCB for earth leakage protection; the 5SY series is for overcurrent protection.

MPN
5SM3312-3