1 A D-curve MCB for motor and transformer branch circuits
The D-curve holds through 10–20× rated current for short-duration starts, then clears on sustained overload.
At 35 °C ambient the breaker carries the full 1 A; at 40 °C it derates to 0.93 A, at 45 °C to 0.89 A, and at 50 °C and 55 °C to 0.8 A. Mount in any position — the quick-assembly system snaps onto standard DIN rail. Three modular width units (54 mm) of DIN space.
Halogen-free and silicon-free construction. Humidity tolerance: max 95% RH up to 55 °C, derating to 35% RH at 75 °C. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Sealable terminals (top and bottom combined).