It carries a 10 kA interrupting rating per IEC 60898-1 at 400 V AC, and 35 kA per IEC 60947-2 — so for most commercial and light industrial panel builds, the 10 kA figure governs the bus bracing requirement, while the 35 kA rating gives headroom if the same breaker is coordinated into a higher-fault industrial distribution board under 60947-2 rules. At 54 mm wide (2 modular width units) and 76 mm deep, it fits standard DIN-rail enclosures without needing extra gutter space behind the rail — the 70 mm installation depth means the breaker body clears most 80 mm deep enclosures.
Dual-standard certification (IEC/EN 60898-1 and IEC/EN 60947-2 plus UL 1077 / CSA C22.2 No.235) means this breaker carries the documentation needed for both European and North American panel approvals — the UL 1077 listing at 5 kA is the limiting figure for US installations, so factor that into the SCCR calculation if the panel ships stateside.
Integration Notes
Sealable design lets the panel builder lock the breaker in the ON or OFF position for lockout/tagout compliance without an external hasp.
Ratings & Environment
The humidity derating table caps relative humidity at 95 % up to 55 °C, then steps down — so in a sealed panel near a dryer or kiln, confirm the internal microclimate stays within the curve. DC rating of 15 kA at 60 V (max 72 V operating) per IEC 60947-2 makes this usable for DC distribution in solar combiner boxes or battery circuits, though the B-curve may trip faster on DC than a C-curve would — verify coordination with the downstream DC loads.