25 A B-curve 4-pole — the selectivity anchor
The 4-pole construction (4P) switches all three phases plus the neutral in a single unit, which simplifies panel wiring and ensures full disconnection on a fault.
DIN-rail fit and temperature derating
Rated current is 25 A at 35 °C ambient. Above that, derate: 23.5 A at 45 °C, 22.98 A at 50 °C, 22.45 A at 55 °C, and 21.9 A at 60 °C. In a sealed panel running at 50 °C, you lose about 8 % of the nominal rating — budget the load accordingly. The surrounding temperature influence curve also caps humidity: 95 % RH up to 55 °C, then 55 % RH up to 70 °C, then 35 % RH up to 75 °C maximum.
Active production, sourced per RFQ
Approvals are implicit in the EN 60898 and IEC 60947-2 ratings — this MCB carries the CE mark for the European low-voltage directive.