Skip to main content
Siemens 5SY4425-6KK11 — 4-Pole MCB (DIN Rail)

Siemens 5SY4425-6KK11 SENTRON MCB, 4P B-25A 10kA

MPN5SY4425-6KK11

Siemens SENTRON 5SY4425-6KK11, 4-pole miniature circuit breaker, B-curve, 25 A, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 72 mm wide, 76 mm deep.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4425-6KK11 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4425-6KK11 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC25 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY4425-6KK11 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-220 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SY4425-6KK11 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4425-6KK11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

Four poles (4P) in a 72 mm wide housing that snaps onto DIN rail — 4 modular width units. Breaking capacity is 10 kA per EN 60898 and 20 kA per IEC 60947-2, which means it clears faults up to 20 kA under the industrial standard, giving headroom for high-fault panels. Designed for railway applications per the product designation, so it carries vibration and temperature cycling tolerance beyond a standard commercial MCB.

The 25 A rating holds at 35 °C ambient; at 40 °C it derates to 24 A, at 50 °C to 22.98 A, and at 60 °C to 21.9 A.

Construction and compliance

Halogen-free and silicon-free construction, sealable, with touch protection on the terminals. Energy limitation class 3 — the arc energy let-through is low enough to protect downstream equipment in a fault. The fastening method uses a quick assembly system (snap-on DIN rail). The product carries the SENTRON brand and is classified per IEC 81346-2 and DIN EN 61346-2 as function F (protection).

Frequently asked questions

What is 5SY4425-6KK11's listed depth (76 mm) on this component line?

The total depth is 76 mm, with an installation depth of 70 mm (the portion behind the panel surface).

What is 5SY4425-6KK11's listed width (72 mm) on this component line?

The width is 72 mm, which corresponds to 4 modular width units on a standard DIN-rail mounting system.

MPN
5SY4425-6KK11