The 5SY4463-5: The A-curve tripping characteristic means it responds to low-level overcurrents — the magnetic trip threshold sits around 2–3× In, making it a fit for semiconductor protection or long cable runs where standard C-curve breakers would be too slow to clear a fault. Thermal derating is published per pole: 58.4 A at 45 °C, 56.83 A at 50 °C, 55.12 A at 55 °C, and 53.42 A at 60 °C.
Breaking capacity and fault clearance
For DC circuits, the same 15 kA rating applies per IEC 60947-2.
The quick-assembly fastening system snaps onto the rail without tools. Mounting position is any orientation — no derating needed for horizontal or inverted mounting.