It switches the neutral conductor (1P+N) inside a 2-pole housing, so you get full isolation on both lines in a single 36 mm wide unit. Rated breaking capacity hits 10 kA under IEC/EN 60898-1 and 20 kA under IEC 60947-2, with a DC rating of 15 kA per IEC 60947-2 at 60 V. That dual-standard rating means it qualifies for both residential-distribution boards (EN 60898) and industrial panel schedules (IEC 60947-2) — one part, two compliance gates.
The combined terminal at top and bottom accepts the same conductor range; supply cord position is arbitrary, so you can feed from either end without flipping the breaker. Sealable terminals let you lock the cover after commissioning for tamper-proofing.
Halogen-free and silicon-free construction — no silicone outgassing to foul relay contacts or optical sensors in the same enclosure. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — survives shipping and moderate machine vibration.