Skip to main content
Siemens 5SY4515-8 — 1-Pole MCB (DIN Rail)

Siemens 5SY4515-8 SENTRON MCB, D Curve, 1.6 A, 2-Pole, 10 kA

MPN5SY4515-8
Active

Siemens SENTRON, miniature circuit breaker, 5SY4515-8, D characteristic, 1.6 A, 2-pole (1P+N), 10 kA (EN 60898) / 35 kA (IEC 60947-2), halogen-free, silicon-free, sealable.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4515-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Application suitabilityMechanical engineering / industry
5SY4515-8 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Rated value (EN 60898)10 kA
Overvoltage categoryIII
5SY4515-8 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4515-8 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY4515-8 is a SENTRON miniature circuit breaker with a D tripping characteristic, rated 1.6 A at AC, designed for 2-pole (1P+N) circuits on 50/60 Hz supplies.

Thermal derating and ambient range

The 1.6 A rating holds at 35 °C; at 45 °C it derates to 1.48 A, at 50 °C to 1.44 A, at 55 °C to 1.4 A, and at 60 °C to 1.36 A. The operating ambient spans -40 °C to 75 °C, with humidity limits up to 95% at 55 °C, tapering to 35% at 75 °C. That covers cold storage and desert installations alike.

Mounting position is any — vertical, horizontal, upside-down — so no panel layout restrictions. The combined terminal at top and bottom accepts the same conductor range, and the breaker is sealable for tamper-proofing in metering or critical circuits.

Materials and compliance

Halogen-free and silicon-free construction means no corrosive off-gassing under fault — relevant for cleanroom-adjacent panels or sealed enclosures with sensitive electronics. The IP20 rating applies with connected conductors; the breaker itself is touch-protected (fingertip-safe) per the product feature. Classified as F per IEC 81346-2 and DIN EN 61346-2. Suitability for mechanical engineering and industry is stated on the listing.

Frequently asked questions

What is the breaking capacity of 5SY4515-8?

10 kA per EN 60898, 35 kA per IEC 60947-2 at AC, and 15 kA per IEC 60947-2 at DC. The higher IEC figure is the one to use for industrial panel SCCR coordination.

What is the difference between 5SY4515-8 and 5SY4301-7CV?

The 5SY4301-7CV is a 1-pole B-curve 1 A MCB; the 5SY4515-8 is a 2-pole (1P+N) D-curve 1.6 A MCB. The D curve handles higher inrush (motors, transformers) and the 1P+N configuration gives you switched neutral. They are not drop-in interchangeable without rewiring the neutral path and checking the trip coordination.

Where can I buy 5SY4515-8?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the latest position.

MPN