It delivers a 10 kA breaking capacity per EN 60898 and 5 kA per UL 1077 / CSA C22.2 No. 235 — enough to clear fault currents in a standard industrial panel without cascading upstream. The C-curve trips between 5-10× rated current, so it holds motor inrush and transformer energization while still protecting branch circuits against hard shorts.
The 16 A rating holds at 35 °C ambient. Above that, the MCB derates: 15.04 A at 40 °C, 14.54 A at 45 °C, 14.02 A at 50 °C, and 13.47 A at 55 °C.
The MCB carries approvals per EN 60898 (10 kA), UL 1077 and CSA C22.2 No. 235 (5 kA). Sealable design allows lockout/tagout. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — holds takt time on a weld-line panel.