Skip to main content
Siemens 5SY6313-6 — 3-Pole MCB (DIN Rail)

Siemens 5SY6313-6 SENTRON MCB, 3P B-Curve, 6kA/15kA

MPN5SY6313-6
Active

Siemens SENTRON 5SY6313-6 miniature circuit breaker, 3-pole, B tripping characteristic, 6 kA (EN 60898-1) / 15 kA (IEC 60947-2) breaking capacity, 400 V AC, 60 V DC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6313-6 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY6313-6 — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 608986 kA
Breaking capacity per IEC 60947-215 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree3
5SY6313-6 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)1.7 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
Rated voltage (AC, single-phase)440 V
5SY6313-6 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes
5SY6313-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

The 6 kA / 15 kA split matters: if the prospective short-circuit current at the panelboard is above 6 kA but under 15 kA, the 5SY6313-6 still clears the fault without upstream coordination issues, provided the installation follows IEC 60947-2. In a UL 1077 supplementary-protector role, the 5 kA limit applies; do not use it as a branch-circuit main without verifying the available fault current. The quick-assembly fastening method and any mounting position give panel builders layout flexibility. Combined top and bottom terminals simplify daisy-chaining busbars.

Standards and environmental

Approved to IEC / EN 60898-1 (MCB standard) and IEC / EN 60947-2 (low-voltage switchgear and controlgear), plus UL 1077 and CSA C22.2 No. 235 for supplementary protection in North American panels.

Frequently asked questions

What is the breaking capacity of 5SY6313-6?

6 kA per EN 60898-1, 15 kA per IEC 60947-2 at 400 V AC and 60 V DC, and 5 kA per UL 1077 / CSA C22.2 No. 235.

Does 5SY6313-6 replace 5SY4140-7?

No direct replacement — the 5SY4140-7 is a 1-pole unit with a different current rating. The 5SY6313-6 is a 3-pole MCB; they serve different circuit configurations. Check the pole count and rating before substituting.

Where can I buy 5SY6313-6?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What compliance documentation is available for 5SY6313-6?

The breaker carries IEC / EN 60898-1, IEC / EN 60947-2, UL 1077, and CSA C22.2 No. 235 approvals. It is halogen-free and silicon-free. RoHS and REACH declarations are standard for the SENTRON series.

MPN
5SY6313-6