Breaking capacity sits at 6 kA per EN 60898 and 5 kA per UL 1077 / CSA C22.2 No. 235, which covers most industrial panel secondary circuits.
Mounting position is any — horizontal, vertical, upside-down — no derating required for orientation.
Thermal derating and environmental limits
Rated 13 A at 35 °C ambient. At 40 °C it's 12.22 A; at 45 °C it's 11.82 A; at 50 °C it's 11.39 A; at 55 °C it's 10.95 A. Humidity tolerance is graded: max 95% RH up to 55 °C, then steps down to 55% at 70 °C and 35% at 75 °C. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — fine for machine-mounted panels but not for direct engine vibration.
Compliance and approvals
Rated under EN 60898 (6 kA) and UL 1077 / CSA C22.2 No. 235 (5 kA) — so it carries the marks for both IEC and North American panels. Halogen-free and silicon-free construction, which matters for clean-room or high-reliability environments where outgassing is a concern. Touch protection is built in (finger-safe terminals when conductors are connected). The product designation per IEC 81346-2 and DIN EN 61346-2 is F (protective device). No neutral conductor switching — this is a 3-pole breaker for line-only protection.