ABB 1SFA897112R7001 — Soft Starters

ABB PSE210 Soft Starter 1SFA897112R7001, 208-600V AC, Modbus

MPN1SFA897112R7001
Active

ABB PSE210 soft starter, 1SFA897112R7001, soft start with torque control, 208...600 V AC, 50/60 Hz, Modbus-RTU, 0...30 s ramp, built-in electronic overload protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

1SFA897112R7001 key specifications
ParameterValue
Terminal typeMain Circuit: Bars
Product main typePSE210
Voltage208 ... 600 V AC
Initial voltage during start30 ... 70 %
Step down voltage special rampNo %
Rated control supply voltage100 ... 250 V AC
Rated control circuit voltage24 V DC
Technical UL (CSA, maximum operating voltage UL, CSA)Main Circuit 600 V
Current limit function1.5 ... 7xIe
Starting capacity at maximum rated current ie4xIe for 10s
Rated operational current - In-Line connection210 A
Technical UL (CSA, horsepower rating UL, CSA)(200 ... 208 V AC) Three Phase 60 Hp

All specifications

1SFA897112R7001 additional specifications
ParameterValue
Rated operational power - In-Line connection(230 V) 59 kW
Rated frequency50/60 Hz
IP ratingacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
ProtocolModbus-RTU
Switch for inside delta connectionNo
Popular downloads (CAD dimensional drawing)2CDC001079B0201
Material compliance (Toxic substances control act - TSCA)2CMT2023-006524
Material compliance (Conflict minerals reporting template)9AKK108467A5658
Technical UL (CSA, tightening torque UL, CSA)Control Circuit 4.4 in·lb
FunctionSoft start with torque control
Ramp time0 ... 30 second [unit of time]
Analog outputs4...20 mA
Run signal relayYes
Tightening torqueControl Circuit 0.5 N·m
Fault signal relayYes
Overload protectionBuilt-in electronic overload protection
Protection functionElectronic overload protection, EOL; Locked rotor protection; Current underload protection
By-pass signal relayYes
Overload signal relayYes
Ambient air temperatureOperation -25 ... +60 °C
Service factor percentage100 %
Object classification codeQ
Popular downloads (EPLAN data)9AAC170222_EPLAN
Signal indication faultRed
Integrated electronic overloadYes
Connecting capacity main circuitHole Diameter 8.5 mm
Signal indication running rGreen
Connecting capacity supply circuitRigid 1 x 2.5
IDEA granular category code4740 >> Soft starter
Signal indication protectionYellow
Connecting capacity control circuitRigid 1 x 2.5 mm²
Signal indication ramping up (Down)Green
Popular downloads (Instructions and manuals)1SFC132427M0201
Signal indication completed start rampGreen
Popular downloads (Data sheet, technical information)1SFC132012C0201
Popular Downloads/Instructions and manuals (Part 2)1SFC132057M0201
Popular Downloads/Instructions and manuals (Part 3)1SFC132060M0201

Product details

What this soft starter does on the line

The ABB PSE210 1SFA897112R7001 is a soft starter with torque control, meaning it ramps voltage to the motor during start rather than slamming it across the line. That ramp time is adjustable from 0 to 30 seconds, and the initial voltage during start can be set between 30 and 70 percent of line voltage. For a pump or conveyor that needs a gentle acceleration curve, this is the parameter that sets the jerk limit. Communication is Modbus-RTU over the control circuit, which runs on 24 V DC. The main circuit terminals are bars — hole diameter 8.5 mm — sized for the 208 to 600 V AC range it operates on. The control supply voltage is separate, 100 to 250 V AC, so the logic stays live even when the motor circuit is off. Built-in electronic overload protection covers locked rotor, current underload, and EOL detection. The current limit function is adjustable from 1.5 to 7 times the motor full-load current, which gives you the headroom to handle high-inertia starts without tripping on the inrush.

Main terminals are rated IP00 per IEC 60529 and IEC 60947-1 — that means no enclosure protection at the terminals themselves, so this unit lives inside a panel or cabinet that provides the overall IP rating. The control circuit connects via rigid 1 x 2.5 mm² wire, torqued to 0.5 N·m. The supply circuit takes the same wire size. Three signal relays are onboard: run, fault, and bypass — all standard for a soft starter that needs to tell the PLC what it's doing.

Frequently asked questions

What is the ramp time range on this soft starter?

The ramp time is adjustable from 0 to 30 seconds, and the initial voltage during start can be set between 30 and 70 percent of the line voltage.

What communication protocol does this unit support?

It uses Modbus-RTU over the 24 V DC control circuit.

Where can I buy 1SFA897112R7001?

This part is sourced and quoted to order against an RFQ through independent distribution, with availability and current pricing confirmed at quote time.

What protection functions are built in?

It includes electronic overload protection, locked rotor protection, current underload protection, and EOL detection. The current limit is adjustable from 1.5 to 7 times the motor full-load current.